Skip to main content
Siemens 3VA1110-3EF32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-3EF32-0AC0 SENTRON MCCB, 100 A, 75.6 kA

MPN3VA1110-3EF32-0AC0

Siemens SENTRON 3VA1110-3EF32-0AC0, molded case circuit breaker, 3-pole, 100 A rated continuous current Iu, 75.6 kA breaking capacity at 240 V, TM240 thermal-magnetic release, 70 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-3EF32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1110-3EF32-0AC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1110-3EF32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1110-3EF32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-3EF32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1110-3EF32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-3EF32-0AC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1110-3EF32-0AC0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current (Iu) at 40 °C ambient, with a TM240 thermal-magnetic release that handles overload and short-circuit protection in one package. Its breaking capacity hits 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — numbers that tell you it's sized for high-fault industrial distribution panels, not light commercial subfeeds.

Thermal derating and the TM240 release

The 100 A rating holds flat from 40 °C to 50 °C, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. That's a gentle slope — you don't lose a full breaker size until you're past 65 °C inside the enclosure, which buys headroom for a tightly packed panel.

The two auxiliary switches HQ are pre-wired to a terminal block; verify the NO/NC assignment against your PLC input card before powering up. No communication module or phase-failure detection on this order code, so if you need remote trip indication beyond the aux contacts, plan a separate monitoring relay.

Frequently asked questions

Where can I buy 3VA1110-3EF32-0AC0 and how is it quoted?

The 3VA1110-3EF32-0AC0 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1110-3EF32-0AC0 at 415 V?

At 415 V the breaking capacity is 52.5 kA, with 75.6 kA at 240 V and 32 kA at 440 V.

MPN
3VA1110-3EF32-0AC0