Breaking capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — figures that define the available fault current it can safely interrupt without upstream coordination failure.
At 55 °C it carries 98 A, at 60 °C it carries 96 A, and at 65 °C it carries 94 A — a gentle slope that buys headroom in warm panels without oversizing the frame.
Dimensions are 130 mm high, 76.2 mm wide, and 70 mm deep — a compact 3-pole footprint that fits standard MCCB mounting patterns in distribution boards and motor control centers.