Skip to main content
Siemens 3VA1110-3EF32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-3EF32-0AF0 SENTRON MCCB, 100 A, 3-Pole, TM24

MPN3VA1110-3EF32-0AF0

Siemens SENTRON 3VA1110-3EF32-0AF0, 3-pole molded case circuit breaker, 100 A at 40 °C, TM240 thermal-magnetic release, 75.6 kA breaking capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-3EF32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11103EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1110-3EF32-0AF0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.25 W
3VA1110-3EF32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1110-3EF32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-3EF32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1110-3EF32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-3EF32-0AF0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Rated 100 A at 40 °C continuous, it carries that rating flat through 50 °C before a mild derate begins — 98 A at 55 °C, 91 A at 70 °C.

Breaking capacity ramps from 75.6 kA at 240 V down to 11.9 kA at 690 V. At 415 V it clears 52.5 kA, which gives headroom for most industrial service-entrance and feeder applications without upstream fusing. The 3VA1110-5ED36-0AC0 sibling uses an electronic ETU release instead of the TM240 thermal-magnetic — if your coordination study calls for adjustable long-time, short-time, and instantaneous settings, that variant is the functional fit; if fixed thermal-magnetic is acceptable, this 3EF32 carries the same frame and footprint.

Panel integration

The 76.2 mm wide body (3 inches) fits standard 3-pole MCCB cutouts. Depth is 70 mm, height 130 mm. Maximum power dissipation is 25 W — check thermal rise in a sealed enclosure. Insulation voltage rated at 800 V.

Frequently asked questions

Where can I buy 3VA1110-3EF32-0AF0?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at 415 V?

It clears 52.5 kA at 415 V, which provides selectivity headroom for most feeder applications without upstream fusing.

Will 3VA1110-3EF32-0AF0 drop into a panel specified around 3VA1110-5ED36-0AC0 without rewiring?

Both use the same 3VA frame and footprint, so physical fit is identical. The key difference is the release: TM240 thermal-magnetic here versus an electronic ETU on the -5ED36 variant. If your coordination study requires adjustable trip settings, the -5ED36 is the correct choice.

MPN
3VA1110-3EF32-0AF0