Siemens 3VA1110-3EF32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-3EF32-0AH0 SENTRON MCCB, 3P, 100A, 75.6kA@24

MPN3VA1110-3EF32-0AH0

Siemens SENTRON 3VA1110-3EF32-0AH0, molded case circuit breaker, 3-pole, 100 A (40 °C), line protection, TM240 release, breaking capacity 75.6 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-3EF32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11103EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1110-3EF32-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.25 W

Protection & Trip Unit

3VA1110-3EF32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1110-3EF32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-3EF32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1110-3EF32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-3EF32-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

MCCB for line protection — 100 A frame, TM240 release

The Siemens SENTRON 3VA1110-3EF32-0AH0 is a 3-pole molded case circuit breaker (MCCB) designed for line protection, carrying a TM240 thermal-magnetic overcurrent release. Rated 100 A continuously at 40 °C, it derates to 91 A at 70 °C — the full current-versus-temperature curve is on record. Breaking capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, and 11.9 kA at 690 V, so it handles high fault currents across common low-voltage distribution levels. The auxiliary switch block includes 2 auxiliary switches plus 1 trip alarm switch (HQ designation), and a local trip indicator is present. Insulation voltage is rated 800 V; maximum power loss is 25 W. Operating temperature range is -25 °C to +70 °C, storage from -40 °C to +80 °C. Dimensions: 130 mm height, 76.2 mm width, 70 mm depth — fits standard SENTRON 3VA panel cutouts and busbar systems. No undervoltage release, no communication function, no ground-fault monitoring on this variant.

MPN
3VA1110-3EF32-0AH0