Sourcing and lifecycle
The auxiliary release is a shunt trip (STL) — order code 3VA9688-0BL33 for the integrated auxiliary trip. The breaker ships with 2 auxiliary switches (HQ version) fitted. No undervoltage release, no voltage trigger beyond the shunt trip itself.
Panel integration
The 3VA1110-3EF32-0KC0 measures 70 mm deep by 76.2 mm wide by 130 mm high. That 76.2 mm width is a standard 3-pole MCCB footprint — it fits the usual DIN-rail or screw-mount panel cutouts without surprises. IP40 on the front means it is protected against tools and small wires entering the front face, but not against hose-down; keep it inside a sealed enclosure if the environment is wet. Storage range spans -40 °C to 80 °C, operating range -25 °C to 70 °C. The 80 °C storage max matters if the breaker sits in a hot warehouse or unventilated shipping container before installation — it will survive the trip. The -25 °C operating minimum covers most unheated electrical rooms in temperate climates.