Skip to main content
Siemens 3VA1110-3EF36-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-3EF36-0AG0 SENTRON MCCB, 100 A, 3-Pole, Line

MPN3VA1110-3EF36-0AG0

Siemens SENTRON 3VA1110-3EF36-0AG0, molded case circuit breaker, 3-pole, 100 A rated continuous current Iu, TM240 thermal-magnetic trip, line protection version, 75.6 kA breaking capacity at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-3EF36-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB11

Ratings

3VA1110-3EF36-0AG0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA

Protection & Trip Unit

3VA1110-3EF36-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1110-3EF36-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-3EF36-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1110-3EF36-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-3EF36-0AG0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1110-3EF36-0AG0 is a 3-pole molded case circuit breaker rated for 100 A continuous current (Iu) with a TM240 thermal-magnetic trip unit, built for line protection in distribution panels. It carries a 75.6 kA breaking capacity at 240 V, stepping down to 52.5 kA at 415 V and 32 kA at 440 V — numbers that tell you it handles high-fault utility feeds without cascading upstream. The 70 mm depth and 76.2 mm width fit standard MCCB panel cutouts, and the front face is IP40 rated, so it's fine for enclosed switchboards but not for washdown areas.

Thermal derating and trip curve

The 100 A rating holds flat from 40 °C up to 50 °C. Above that it derates: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. If your panel ambient runs hot, size the load accordingly — the breaker won't nuisance-trip, but the continuous current limit drops. The TM240 thermal-magnetic trip has a fixed time delay tr max of 1 s, so it coordinates with downstream feeders on moderate overloads.

Panel fit and integration

At 76.2 mm wide and 70 mm deep, this breaker drops into a standard 3-pole MCCB slot. The front IP40 rating means it's protected against solid objects larger than 1 mm but not against water ingress — keep it inside a closed panel. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C, so it handles cold warehouses and hot shipping containers without issue.

Frequently asked questions

Where can I buy 3VA1110-3EF36-0AG0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 3VA1110-3EF36-0AG0 at different voltages?

75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V — the interrupting rating drops as voltage rises, which is typical for MCCBs.

What is the width and depth of this MCCB?

Width is 76.2 mm, depth is 70 mm — fits standard 3-pole MCCB panel cutouts.

MPN
3VA1110-3EF36-0AG0