It is a 3-pole unit rated 100 A continuously at 40 °C, with a maximum interrupting capacity of 75.6 kA at 240 V AC.
Breaking capacity across voltages
The interrupting rating drops as system voltage rises: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V.
Above that it derates: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, 91 A at 70 °C. Dimensions: 76.2 mm wide (3 in), 130 mm tall (5.12 in), 70 mm deep (2.76 in).