The TM240 thermal-magnetic overcurrent release handles the overload and short-circuit trip curve, while the integrated undervoltage release (UVR) provides a controlled dropout under voltage-loss conditions. Breaking capacity runs from 75.6 kA at 240 V down to 10.5 kA at 690 V, so the spec sheet on the system's available fault current determines which voltage tap governs the installation.
The 100 A rating holds flat through 50 °C ambient; above that it derates to 96 A at 55 °C and 90 A at 70 °C. Physical footprint is 76.2 mm wide by 130 mm tall by 70 mm deep — a 3-pole MCCB that fits standard DIN-rail or panel-mount cutouts for the SENTRON family.
Auxiliary Contacts and Trip Indication
The auxiliary release is an undervoltage release (UVR) — part number 3VA9608-0BB24 for the integrated trip unit.