Breaking capacity runs 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V and 690 V — figures that govern fault-clearing capability at the point of common coupling. The TM240 release is fixed-thermal, fixed-magnetic, so coordination studies rely on the published trip curve rather than field-adjustable settings.
The breaker carries a full 100 A from 40 °C through 50 °C, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Maximum power loss is 25 W.
The 3VA1110-3EF36-0KA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep. The 3-pole, 100 A frame mounts into standard SENTRON panelboard and MCCB enclosures.