Skip to main content
Siemens 3VA1110-3GF42-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-3GF42-0AH0 SENTRON MCCB, 100 A, 4-Pole, 75.6

MPN3VA1110-3GF42-0AH0

Siemens SENTRON 3VA1110-3GF42-0AH0, 4-pole molded case circuit breaker, 100 A, TM240 thermal-magnetic release, 75.6 kA breaking capacity at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-3GF42-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA11103GF420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1110-3GF42-0AH0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.25 W

Protection & Trip Unit

3VA1110-3GF42-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA1110-3GF42-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-3GF42-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1110-3GF42-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-3GF42-0AH0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

What this MCCB carries and where it fits

The Siemens 3VA1110-3GF42-0AH0 is a SENTRON 4-pole molded case circuit breaker rated 100 A continuous at 40 °C, with a TM240 thermal-magnetic trip unit. It's a line-protection device — no undervoltage release, no communication module, no ground-fault monitoring. The 100 A holds flat from 40 °C up to 50 °C; above that it derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. That thermal curve matters if this breaker lives in a hot enclosure next to other dissipating gear. Breaking capacity steps with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. For a 480 V panel this lands between the 440 V and 500 V curves — the 32 kA at 440 V is the closest published figure, and the 11.9 kA at 500 V is conservative for 480 V. Rated insulation voltage is 800 V. Front IP40 protection keeps dust out of the breaker face; the rest of the case is open to the enclosure environment. Auxiliary contact version is 2 auxiliary switches plus 1 trip alarm switch (HQ type). The basic switch assembly part is 3VA11103GF420AA0.

Panel fit and mounting

The 3VA1110-3GF42-0AH0 measures 130 mm high, 101.6 mm wide, 70 mm deep. Four-pole width at 101.6 mm is standard for a 4-pole MCCB in this class — it occupies the same footprint as other SENTRON 3VA frame breakers. Mounts on a DIN rail or with screw-mount lugs; the IP40 front is the only exposed face.

Frequently asked questions

What is the breaking capacity of 3VA1110-3GF42-0AH0 at 415 V?

52.5 kA at 415 V. At 240 V it's 75.6 kA, at 440 V it's 32 kA, and at 500 V / 690 V it's 11.9 kA.

Where can I buy 3VA1110-3GF42-0AH0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
3VA1110-3GF42-0AH0