Skip to main content
Siemens 3VA1110-4EE32-0AA0-ZD00 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-4EE32-0AA0-ZD00 Circuit Breaker, 100A, 36kA

MPN3VA1110-4EE32-0AA0-ZD00

Siemens 3VA1 IEC frame 160, breaking capacity class S, Icu=36kA @ 415V, 3-pole, line protection TM220, ATFM, In=100A, overload protection Ir=70A...100A, short-circuit protection Ii=10 x In, nut keeper kit for DC Power OEM in China.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

What this breaker is and what it does

The Siemens 3VA1110-4EE32-0AA0-ZD00 is a 3VA1 IEC frame 160 molded case circuit breaker (MCCB) rated for 100 A continuous current, with a 36 kA interrupting capacity at 415 V AC (breaking capacity class S). That 36 kA rating means it can safely clear a fault current up to that level without welding its contacts or rupturing the case — critical for downstream equipment protection and panel integrity in a high-fault installation. It's a 3-pole unit with a TM220 thermal-magnetic trip unit (ATFM), adjustable overload protection (Ir) from 70 A to 100 A, and a fixed short-circuit protection (Ii) at 10 times the rated current (In). The 10x In setting gives you a magnetic trip at roughly 1000 A, which is typical for general-purpose motor and feeder protection in IEC distribution boards. This variant also includes a nut keeper kit, specified for a DC Power OEM application in China — so the hardware package is already matched for that customer's panel-build standard.

Where it fits in the panel

The 3VA1 frame 160 mounts on a DIN rail or can be screw-fixed to a backplate. At 100 A, you'll want to watch the heat dissipation in a tightly packed enclosure — the TM220 trip's thermal element responds to ambient temperature, so derate if the panel runs hot. Keep at least 25 mm clearance above and below for arc gases to vent.

Frequently asked questions

What is the breaking capacity of this breaker?

It has an Icu of 36 kA at 415 V AC, which is the maximum fault current it can safely interrupt under standard IEC test conditions.

How do I get pricing and availability for this part?

This configured variant is sourced to order against an RFQ. Submit a request through the distributor and they will confirm current pricing and availability at quote time.

What is the overload protection range on this breaker?

The adjustable overload protection (Ir) ranges from 70 A to 100 A, set via the TM220 thermal-magnetic trip unit.

MPN
3VA1110-4EE32-0AA0-ZD00