The 3VA1110-4EF32-0HA0: Rated breaking capacity is 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V.
Thermal derating and ambient range
Carries full 100 A up to 50 °C ambient; above that it derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C.
Mounts on a DIN rail or panel — 76.2 mm wide (roughly 3 x 25.2 mm per pole), 130 mm tall, 70 mm deep. No auxiliary contacts or communication module on this build — the shunt trip is the only auxiliary release.
Listed as current production. No PCN or EOL notice on this order code.