Skip to main content
Siemens 3VA1110-4EF32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-4EF32-0HC0 SENTRON MCCB, 100A, 3-Pole, 121kA

MPN3VA1110-4EF32-0HC0

Siemens SENTRON 3VA1110-4EF32-0HC0, molded case circuit breaker, 3-pole, 100 A rated at 40 °C, 121 kA breaking capacity at 240 VAC, line protection design with shunt trip release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-4EF32-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11104EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1110-4EF32-0HC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.25 W

Protection & Trip Unit

3VA1110-4EF32-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1110-4EF32-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-4EF32-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1110-4EF32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-4EF32-0HC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

MCCB for line protection — 100 A frame, high interrupting capacity

The Siemens SENTRON 3VA1110-4EF32-0HC0 is a 3-pole molded case circuit breaker (MCCB) rated for continuous current of 100 A at 40 °C, with no derating needed up to 50 °C — it holds 100 A through that range, then steps down to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. The interrupting capacity reaches 121 kA at 240 VAC, 75.6 kA at 415 VAC, 52.5 kA at 440 VAC, and 11.9 kA at both 500 VAC and 690 VAC — numbers that govern selectivity coordination in high-fault panels. Rated insulation voltage is 800 V. The breaker is designed for line protection (cable/feeder protection), not motor or generator duty, and ships with a shunt trip release (STL) plus two HQ auxiliary switches built in.

Integration — panel footprint and auxiliary wiring

The breaker occupies 76.2 mm width (3 in), 130 mm height (5.12 in), and 70 mm depth (2.76 in) — a standard SENTRON 3VA frame size that fits existing DIN-rail or panel-mount cutouts for this series. The shunt trip release (STL) and two auxiliary switches (HQ) are pre-installed, so no field-add kit is needed for remote trip or status feedback. Maximum power loss is 25 W, which factors into enclosure thermal calculations. Operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C.

Configuration — base switch variant and release options

The supplied basic switch is order code 3VA11104EF320AA0. This variant includes a shunt trip (STL) undervoltage release is not present (no undervoltage release, no ground-fault monitoring, no communication function, no trip indicator). The design is line protection — not suited for motor circuit protection without additional overload relay. The two auxiliary switches (HQ) provide status signaling for the open/closed position.

Frequently asked questions

What is the breaking capacity of 3VA1110-4EF32-0HC0 at different voltages?

The interrupting capacity is 121 kA at 240 VAC, 75.6 kA at 415 VAC, 52.5 kA at 440 VAC, and 11.9 kA at both 500 VAC and 690 VAC.

What auxiliary options come on this MCCB?

It includes a shunt trip release (STL) and two HQ auxiliary switches pre-installed. There is no undervoltage release, no ground-fault monitoring, and no communication function.

Where can I buy 3VA1110-4EF32-0HC0 and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
3VA1110-4EF32-0HC0