Siemens 3VA1110-4EF32-0JH0 SENTRON MCCB, 100 A, 3-Pole, 121

MPN3VA1110-4EF32-0JH0

Siemens SENTRON 3VA1110-4EF32-0JH0, molded case circuit breaker, 3-pole, 100 A rated continuous current Iu, TM240 overcurrent release, 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, 11.9 kA at 690 V, line protection version, shunt trip (STL), 2 auxiliary switches + 1 trip alarm switch HQ, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-4EF32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1110-4EF32-0JH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1110-4EF32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1110-4EF32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-4EF32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1110-4EF32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-4EF32-0JH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Siemens 3VA1110-4EF32-0JH0 — 100 A MCCB with TM240 Release

Its TM240 thermal-magnetic overcurrent release handles the overload and short-circuit protection for feeder and distribution circuits in commercial and industrial panels. The interrupting ratings climb to 121 kA at 240 V AC and 75.6 kA at 415 V AC — numbers that tell you this breaker can clear high-fault conditions without cascading upstream, which is the deciding factor for panel SCCR compliance.

The TM240 release means the thermal element is calibrated for a 240 A frame — the breaker's continuous rating is set by the installed trip unit, not the frame. That gives you headroom to swap in a higher-rated trip later if the load grows, without pulling the breaker out of the panel. The auxiliary contacts let the PLC or BMS know the breaker state without adding a separate contactor block.

The breaker measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that drops into most DIN-rail or panel-mount enclosures without re-drilling. The IP40 front protection means it's suited for indoor panel use where no water jets are present; keep it behind a locked door in washdown zones.

Frequently asked questions

Where can I buy 3VA1110-4EF32-0JH0 and what is the lead time?

This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time and price commitment.

What are the interrupting ratings for 3VA1110-4EF32-0JH0?

121 kA at 240 V AC, 75.6 kA at 415 V AC, 52.5 kA at 440 V AC, and 11.9 kA at 690 V AC. These ratings govern the maximum fault current the breaker can safely clear at each voltage level.

What auxiliary contacts does this MCCB include?

It comes with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration), and a shunt trip (STL) for remote tripping.

What is the ambient temperature derating curve for 3VA1110-4EF32-0JH0?

Rated 100 A from 40 °C to 50 °C, then 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. No derating needed below 50 °C.