Skip to main content
Siemens 3VA1110-4EF36-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-4EF36-0AD0 SENTRON MCCB, 100 A, 3-Pole, 121

MPN3VA1110-4EF36-0AD0

Siemens SENTRON 3VA1110-4EF36-0AD0, molded case circuit breaker, 3-pole, 100 A (40 °C), 121 kA interrupting at 240 V, line protection design, TM240 release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-4EF36-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11104EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1110-4EF36-0AD0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.25 W

Protection & Trip Unit

3VA1110-4EF36-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1110-4EF36-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-4EF36-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1110-4EF36-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-4EF36-0AD0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB carries — and what it protects

The Siemens SENTRON 3VA1110-4EF36-0AD0 is a 3-pole molded case circuit breaker rated 100 A at 40 °C, with a TM240 thermal-magnetic release designed for line protection. Its interrupting rating hits 121 kA at 240 V AC — that is the fault current it can safely clear without welding contacts or venting arc gas into the panel. At 415 V it still interrupts 75.6 kA, and at 690 V it holds 11.9 kA. The rated insulation voltage is 800 V, so the internal clearances are sized for 480 V and 600 V class distribution panels without derating the basic impulse level. This is not a motor-protective breaker — the TM240 release is a fixed thermal-magnetic curve for feeder and distribution protection. It carries 100 A continuously up to 50 °C, then derates to 91 A at 70 °C. The 25 W maximum power loss at rated current matters for enclosed panel heat budgets; if you are packing multiple breakers into a small enclosure, that figure drives the ventilation calculation.

Panel fit and mounting

The 3VA1110-4EF36-0AD0 measures 76.2 mm wide by 130 mm tall by 70 mm deep — a standard 3-pole MCCB footprint that fits SENTRON distribution boards and most DIN-rail-mount enclosures with the appropriate adapter. The 70 mm depth keeps it clear of gland plates and backpanel wiring troughs in 200 mm deep enclosures. Three auxiliary switches (HQ design) can be stacked on the side without increasing the width beyond the 76.2 mm frame.

Frequently asked questions

Where can I buy 3VA1110-4EF36-0AD0 and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response.

What is the interrupting rating of 3VA1110-4EF36-0AD0 at 240 V?

121 kA at 240 V AC. At 415 V it interrupts 75.6 kA, and at 690 V it holds 11.9 kA.

What is the rated current of 3VA1110-4EF36-0AD0 at 40 °C?

100 A at 40 °C, with no derating needed up to 50 °C. At 70 °C it derates to 91 A.

Does 3VA1110-4EF36-0AD0 include a ground-fault monitoring function?

No — this is a line-protection MCCB without ground-fault monitoring. The ground-fault monitoring version is specified separately.

MPN
3VA1110-4EF36-0AD0