Siemens 3VA1110-4EF36-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-4EF36-0AF0 Circuit Breaker, 100A, 36kA @ 415

MPN3VA1110-4EF36-0AF0

Siemens 3VA1 IEC frame 160, breaking capacity class S, 3-pole, line protection TM240, ATAM, In=100A, overload protection Ir=70A...100A, short-circuit protection Ii=5...10 x In, clamp connection, 1 auxiliary switch HQ, 1 trip alarm switch HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

3VA1110-4EF36-0AF0 — IEC Frame 160 MCCB, 100 A, 36 kA at 415 V

The Siemens 3VA1110-4EF36-0AF0 is a 3-pole molded-case circuit breaker in the 3VA1 series, built on the IEC frame-160 platform. It carries a breaking capacity class S rating of Icu = 36 kA at 415 V AC — meaning it can safely interrupt fault currents up to that level without upstream cascading, per IEC 60947-2. That makes it suitable for distribution panels and motor control centers where high available fault current is expected.

Trip Unit and Protection Settings

Fitted with a TM240 thermal-magnetic trip unit. The thermal element (overload) is adjustable from Ir = 70 A to 100 A, matching the In = 100 A frame rating. The magnetic (short-circuit) pickup Ii is adjustable between 5 and 10 times In — that is 500 A to 1000 A. This adjustability lets the panel builder coordinate with downstream feeders without swapping the breaker body.

Integrated Auxiliary and Alarm Switching

Includes one auxiliary switch HQ and one trip-alarm switch HQ. The auxiliary reports the breaker's open/closed position; the alarm switch changes state only when the breaker trips on a fault. Both are wired via clamp terminals — no separate add-on module needed for basic status feedback to a PLC or annunciator panel.

Frequently asked questions

What is the breaking capacity of 3VA1110-4EF36-0AF0?

Icu = 36 kA at 415 V AC, breaking capacity class S per IEC 60947-2. This is the maximum short-circuit current the breaker can safely interrupt at that voltage.

Where can I buy the 3VA1110-4EF36-0AF0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What are the trip settings on this breaker?

Thermal overload Ir adjustable 70 A to 100 A. Magnetic short-circuit pickup Ii adjustable 5 to 10 times In (500 A to 1000 A). The trip unit is a TM240 thermal-magnetic type.