Skip to main content
Siemens 3VA1110-4EF36-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1110-4EF36-0BA0 MCCB, 100 A, 3-Pole, 121

MPN3VA1110-4EF36-0BA0

Siemens SENTRON 3VA1110-4EF36-0BA0, molded case circuit breaker (MCCB), 100 A, 3-pole, TM240 thermal-magnetic release, 121 kA at 240 V, 75.6 kA at 415 V, IP40 front, 70 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-4EF36-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1110-4EF36-0BA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1110-4EF36-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1110-4EF36-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-4EF36-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1110-4EF36-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-4EF36-0BA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1110-4EF36-0BA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous at 40 °C, with a TM240 thermal-magnetic trip unit — meaning the thermal element handles overloads and the magnetic element handles short-circuits, no electronic adjustments. Breaking capacity hits 121 kA at 240 V and 75.6 kA at 415 V, so it handles high-fault industrial feeds without cascading upstream.

The 100 A rating holds steady up to 50 °C, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C — a shallow curve that buys headroom in a warm cabinet. Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep; the 76.2 mm width is a standard 3-pole MCCB footprint, so it drops into most panel-mount cutouts without re-drilling.

Frequently asked questions

What is the breaking capacity of 3VA1110-4EF36-0BA0 at 415 V?

75.6 kA at 415 V AC. At 240 V it is 121 kA, at 440 V it is 52.5 kA, and at 690 V it is 11.9 kA.

Will 3VA1110-4EF36-0BA0 drop into a panel specified for 3VA1112-5EF32-0CA0 without rewiring?

The 3VA1110-4EF36-0BA0 shares the same 3-pole, 100 A class and SENTRON platform as 3VA1112-5EF32-0CA0, so the footprint and bus-bar spacing are the same. The difference is in the trip unit and breaking capacity — verify the interrupting rating at your fault level before swapping.

Where can I buy 3VA1110-4EF36-0BA0 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
3VA1110-4EF36-0BA0