Skip to main content
Siemens 3VA1110-4FD42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-4FD42-0AA0 SENTRON MCCB, 100 A, 4-Pole, 121

MPN3VA1110-4FD42-0AA0
Active

Siemens SENTRON 3VA1110-4FD42-0AA0, molded case circuit breaker, 4-pole, 100 A, line protection, TM210 thermal-magnetic release, breaking capacity 121 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-4FD42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1110-4FD42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.25 W
3VA1110-4FD42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1110-4FD42-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-4FD42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1110-4FD42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-4FD42-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1110-4FD42-0AA0 is a 4-pole molded case circuit breaker rated for 100 A continuous current at 40 °C, with a TM210 thermal-magnetic release for line protection. Its breaking capacity reaches 121 kA at 240 V AC, dropping to 75.6 kA at 415 V and 52.5 kA at 440 V — numbers that matter for fault-current coordination studies on the distribution side of a transformer.

The breaker holds its full 100 A rating up to 50 °C ambient; above that it derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Maximum power loss is 25 W. In a crowded panel, that thermal curve tells you whether you need to leave a slot open or shift the breaker to a cooler zone.

The 3VA1110-4FD42-0AA0 measures 70 mm deep, 101.6 mm wide, and 130 mm high. Front face is IP40 rated. It accepts an optional motor drive for remote trip or reset. The 4-pole width (101.6 mm) matches the standard SENTRON 3VA frame footprint — it drops into the same DIN-rail or screw-mount position as other 4-pole 3VA breakers without re-drilling the backplate.

Frequently asked questions

Where can I buy 3VA1110-4FD42-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1110-4FD42-0AA0 at 415 V?

75.6 kA at 415 V AC, which covers most industrial low-voltage distribution fault levels.

What is the depth of 3VA1110-4FD42-0AA0?

70 mm — that's the body depth, not counting any handle or accessory protrusion.

Will 3VA1110-4FD42-0AA0 drop into a panel built for 3VA1110-5EF36-0AD0?

Both are 4-pole 3VA frame breakers with the same 101.6 mm width and 130 mm height, so the mounting footprint is identical. The difference is in the release and breaking capacity — verify the trip curve and fault rating match your coordination study before swapping.

MPN
3VA1110-4FD42-0AA0