Skip to main content
Siemens 3VA1110-4FF42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-4FF42-0AA0 SENTRON MCCB, 100 A, 4-Pole, TM24

MPN3VA1110-4FF42-0AA0
Active

Siemens SENTRON 3VA1110-4FF42-0AA0, 4-pole molded case circuit breaker, 100 A continuous, TM240 thermal-magnetic release, interrupting ratings 121 kA at 240 V, 75.6 kA at 415 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-4FF42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1110-4FF42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.25 W

Protection & Trip Unit

3VA1110-4FF42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA1110-4FF42-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-4FF42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1110-4FF42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-4FF42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

Thermal Derating and Ambient Conditions

The 3VA1110-4FF42-0AA0: Continuous current rating holds at 100 A up to 50 °C, then derates linearly: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C. Maximum power loss is 25 W. The front face carries IP40 protection — suitable for dry indoor panel environments, not washdown zones.

Dimensions and Panel Fit

The breaker measures 130 mm high, 101.6 mm wide, and 70 mm deep. Four-pole width at 101.6 mm is standard for this class; verify DIN-rail or screw-mount spacing against the existing panel cutout. N-conductor protection is set at 50% of the phase rating. An optional motor drive is available for remote operation.

Sourcing and Lifecycle

The 3VA1110-4FF42-0AA0 is listed as current production — no end-of-life notice on record. Sourced to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

Frequently asked questions

What are the physical dimensions of 3VA1110-4FF42-0AA0?

130 mm high, 101.6 mm wide, 70 mm deep.

MPN