The interrupting rating hits 121 kA at 240 V AC, 75.6 kA at 415 V, and 52.5 kA at 440 V, tapering to 11.9 kA at 500 V and 690 V — figures that govern SCCR coordination in the downstream panel.
That matters for a crowded enclosure where internal temperature rise is a given — the 70 mm depth and 101.6 mm width fit a standard MCCB footprint, and the IP40 front means it's protected against solid objects over 1 mm but not sealed against moisture.
Specs Summary