Skip to main content
Siemens 3VA1110-4GD46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-4GD46-0AA0 SENTRON MCCB, 100 A, 4-Pole, 121

MPN3VA1110-4GD46-0AA0
Active

Siemens SENTRON 3VA1110-4GD46-0AA0, 4-pole molded case circuit breaker, 100 A, TM210 overcurrent release, 121 kA at 240 V, IP40 front, line protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-4GD46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1110-4GD46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.25 W
3VA1110-4GD46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1110-4GD46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-4GD46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1110-4GD46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-4GD46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

The interrupting rating hits 121 kA at 240 V AC, 75.6 kA at 415 V, and 52.5 kA at 440 V, tapering to 11.9 kA at 500 V and 690 V — figures that govern SCCR coordination in the downstream panel.

That matters for a crowded enclosure where internal temperature rise is a given — the 70 mm depth and 101.6 mm width fit a standard MCCB footprint, and the IP40 front means it's protected against solid objects over 1 mm but not sealed against moisture.

Specs Summary

Insulation voltage rated at 800 V. Maximum power loss 25 W. No trip indicator, no voltage trigger, no communication function. The overcurrent release design is TM210. For DC switching applications, the manufacturer directs to the 3VA molded case circuit breaker device manual.

Frequently asked questions

Where can I buy 3VA1110-4GD46-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm price and lead time.

What are the interrupting ratings for 3VA1110-4GD46-0AA0 at different voltages?

121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.

What is the thermal derating for 3VA1110-4GD46-0AA0 above 50 °C?

The breaker holds 100 A up to 50 °C, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C.

MPN
3VA1110-4GD46-0AA0