Siemens 3VA1110-5ED22-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-5ED22-0AA0 SENTRON MCCB, 100A 2-Pole, 187kA

MPN3VA1110-5ED22-0AA0
Active

Siemens SENTRON 3VA1110-5ED22-0AA0, Molded case circuit breaker, 2-pole, 100 A at 40 °C, 187 kA at 240 V AC, TM210 release, line protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1110-5ED22-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1110-5ED22-0AA0 — Ratings
ParameterValue
Number of poles2
Rated operational voltage Ue (AC)415 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Power loss, max.16.66 W
3VA1110-5ED22-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1110-5ED22-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-5ED22-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1110-5ED22-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-5ED22-0AA0 — Mechanical
ParameterValue
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.12 in
Width (in)2 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1110-5ED22-0AA0 is a 2-pole molded case circuit breaker (MCCB) rated for line protection, carrying 100 A continuously at 40 °C and holding that rating flat through 50 °C before a gentle derate curve — 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. That means in a warm panel you keep nearly full ampacity; no need to oversize for a 50 °C ambient. The TM210 thermal-magnetic release is fixed, non-interchangeable, tuned for line protection duty.

At 70 mm deep, 50.8 mm wide, and 130 mm tall, this 2-pole MCCB fits standard SENTRON 3VA panel footprints. Ground-fault monitoring is not included. The neutral conductor is not upgradeable.

Frequently asked questions

How do I get current pricing and availability for 3VA1110-5ED22-0AA0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through our independent distribution network.

What is 3VA1110-5ED22-0AA0's interrupting capacity at 240 V?

187 kA at 240 V AC, and 121 kA at 415 V AC — high enough for most distribution and transformer-secondary applications.

What does the TM210 release designation mean?

TM210 indicates a fixed thermal-magnetic release tuned for line protection — the thermal element handles overloads, the magnetic element handles short circuits. It is not field-interchangeable.

What compliance documentation is available for this MCCB?

The SENTRON 3VA series carries IEC 60947-2 certification. RoHS and REACH compliance documentation is available from Siemens upon request. The reference code per IEC 81346-2 is Q.