Siemens 3VA1110-5ED26-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-5ED26-0AA0 SENTRON MCCB, 100A, 2-Pole, 187kA

MPN3VA1110-5ED26-0AA0
Active

Siemens SENTRON 3VA1110-5ED26-0AA0, Molded case circuit breaker, 2-pole, 100 A at 40 °C, 187 kA interrupting at 240 V AC, TM210 release, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1110-5ED26-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1110-5ED26-0AA0 — Ratings
ParameterValue
Number of poles2
Rated operational voltage Ue (AC)415 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Power loss, max.16.66 W
3VA1110-5ED26-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1110-5ED26-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-5ED26-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1110-5ED26-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-5ED26-0AA0 — Mechanical
ParameterValue
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.12 in
Width (in)2 in
Depth (in)2.76 in

Product details

What this MCCB brings to a panel

The Siemens 3VA1110-5ED26-0AA0 is a 2-pole SENTRON molded case circuit breaker rated 100 A continuous at 40 °C, with a TM210 thermal-magnetic release. The IP40 front rating means it's fine inside a panel enclosure; no washdown capability here.

Thermal derating — the real-world current

This breaker holds its full 100 A rating up through 50 °C ambient. At 55 °C it derates to 98 A, at 60 °C to 96 A, and at 70 °C to 91 A.

The 3VA1110-5ED26-0AA0 measures 70 mm deep, 50.8 mm wide, and 130 mm tall. That 2-inch width is the standard 2-pole MCCB footprint — it drops into the same panel cutout and bus-bar spacing as other 2-pole SENTRON frames. No need to re-drill or re-bus a panel that was laid out for a 3VA1 family breaker.

Frequently asked questions

How do I get current pricing and availability for 3VA1110-5ED26-0AA0?

Submit an RFQ through this listing. We source it to order; pricing and stock availability are confirmed at quote time.

Will 3VA1110-5ED26-0AA0 drop into a panel specified around 3VA1110-5MH36-0AA0 without rewiring?

Both are 2-pole SENTRON MCCBs in the 3VA1 family, sharing the same 50.8 mm width and 130 mm height. The 3VA1110-5ED26-0AA0 uses a TM210 thermal-magnetic release rated 100 A, while the 3VA1110-5MH36-0AA0 carries a different release curve. Footprint and bus-bar spacing are identical — it's a drop-in fit, but verify the trip curve matches your coordination study.

What compliance documentation does Siemens provide for 3VA1110-5ED26-0AA0?

As a current-production SENTRON MCCB, it carries the usual Siemens declarations: CE marking for the European market, UL/CSA listings per the 3VA series, and RoHS/REACH compliance documentation available through Siemens Industry Online Support.

MPN
3VA1110-5ED26-0AA0