Skip to main content
Siemens 3VA1110-5ED32-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-5ED32-0AE0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA1110-5ED32-0AE0

Siemens SENTRON series, molded case circuit breaker (MCCB), order code 3VA1110-5ED32-0AE0, 3-pole, 100 A rated current at 40 °C, breaking capacity 187 kA at 240 V AC, TM210 thermal-magnetic release, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-5ED32-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11105ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1110-5ED32-0AE0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.25 W
3VA1110-5ED32-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1110-5ED32-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-5ED32-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA1110-5ED32-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-5ED32-0AE0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1110-5ED32-0AE0 is a 3-pole molded case circuit breaker (MCCB) rated for line-protection duty, carrying a continuous current of 100 A at 40 °C ambient and derating to 91 A at 70 °C. Its TM210 thermal-magnetic release provides overload and short-circuit protection for feeder and distribution circuits in industrial switchboards and panelboards. The interrupting capacity reaches 187 kA at 240 V AC, 121 kA at 415 V, and 75.6 kA at 440 V — figures that cover most low-voltage fault scenarios without requiring upstream current-limiting fuses.

Breaking Capacity and Thermal Performance

The thermal derating curve is documented: full 100 A up to 50 °C, then 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. For panel builders, this means no forced derating in a standard 40 °C enclosure, but a 9 % reduction if the internal ambient reaches 70 °C.

Physical Dimensions and Panel Integration

The breaker occupies a 76.2 mm width (3 in), 130 mm height (5.12 in), and 70 mm depth (2.76 in). This 3-pole footprint matches the standard SENTRON 3VA molded-case envelope, allowing direct replacement within the same family without re-drilling the mounting plate or re-routing busbars. The depth of 70 mm clears most shallow gland-plate enclosures, though the rear-mounted terminals require at least 50 mm of bending radius for 70 mm² cable lugs. Maximum power loss is 25 W at rated current — relevant for thermal calculations inside sealed cabinets.

Auxiliary Switching and Release Configuration

This variant ships with four HQ-type auxiliary switches (two form-C contacts each, configurable for status indication or remote tripping) and the basic switch 3VA11105ED320AA0. The rated insulation voltage is 800 V, and the operating temperature range spans -25 °C to 70 °C, with storage from -40 °C to 80 °C.

Frequently asked questions

Where can I buy 3VA1110-5ED32-0AE0 and how do I get a price?

This part is sourced to order through independent industrial distribution. Submit an RFQ for current availability and pricing — figures are confirmed at quote time and vary with market conditions.

What is the breaking capacity of 3VA1110-5ED32-0AE0 at 240 V?

The interrupting rating is 187 kA at 240 V AC, per the manufacturer's specification. At 415 V it is 121 kA, at 440 V it is 75.6 kA, and at 500/690 V it is 17 kA.

What are the physical dimensions of 3VA1110-5ED32-0AE0?

Width is 76.2 mm (3 in), height is 130 mm (5.12 in), and depth is 70 mm (2.76 in). This is the standard 3-pole SENTRON 3VA footprint.

What compliance documentation does Siemens provide for this MCCB?

The SENTRON 3VA series carries IEC 60947-2 and UL 489 certifications. RoHS and REACH declarations are standard with the manufacturer's documentation package. Specific certificates are available on request.

MPN
3VA1110-5ED32-0AE0