Skip to main content
Siemens 3VA1110-5ED32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1110-5ED32-0AG0 MCCB, 100 A, 3-Pole

MPN3VA1110-5ED32-0AG0

Siemens SENTRON series, molded case circuit breaker, 3VA1110-5ED32-0AG0, 100 A, 3-pole, TM210 thermal-magnetic release, 187 kA at 240 V, 70 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-5ED32-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11105ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA1110-5ED32-0AG0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.25 W
3VA1110-5ED32-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1110-5ED32-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-5ED32-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1110-5ED32-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-5ED32-0AG0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1110-5ED32-0AG0 is a 3-pole molded case circuit breaker rated for 100 A continuous at 40 °C, with a TM210 thermal-magnetic release for line protection. It carries a 187 kA interrupting capacity at 240 V, dropping to 121 kA at 415 V and 75.6 kA at 440 V — enough headroom for most industrial service-entrance or feeder duty where fault currents run high.

Compared to the 3VA1110-5ED32-0AA0 — which shares the same frame and TM210 release — the -0AG0 adds a factory-installed auxiliary switch (1 N/O + 1 N/C) and a separate trip-alarm switch. If your BOM calls for remote status feedback without wiring an external accessory block, the -0AG0 saves a DIN slot and the labor to fit it. The -0AA0 is the bare breaker; this one ships ready for indication.

Mounts on DIN rail (76.2 mm wide, 130 mm tall, 70 mm deep) — standard panel footprint for a 100 A frame. The TM210 release is fixed thermal-magnetic, so no adjustment dial; you size the breaker to the load and leave it.

Frequently asked questions

Where can I buy 3VA1110-5ED32-0AG0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What is 3VA1110-5ED32-0AG0's interrupting capacity?

187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500 V and 690 V.

Does 3VA1110-5ED32-0AG0 include auxiliary contacts?

Yes, it ships with one auxiliary switch (1 N/O + 1 N/C) and one trip-alarm switch factory-installed.

MPN
3VA1110-5ED32-0AG0