The 3VA1110-5ED32-0AH0 is a Siemens SENTRON 3-pole MCCB rated for line-protection duty — meaning it sits at the feeder or main branch in a distribution panel, not on a motor or a specific load. Its continuous current holds 100 A from 40 °C through 50 °C without derating, then drops to 98 A at 55 °C and 91 A at 70 °C (the operating maximum). That thermal curve matters: if your panel ambient runs at 55 °C, you lose 2 A off the nameplate; at 65 °C you lose 6 A. The TM210 thermal-magnetic release gives a fixed thermal pickup plus magnetic trip for short-circuit events — no electronic adjustment, so it's a set-and-forget part for standard distribution. At 240 V it clears 187 kA — that's the highest single rating on the ledger and covers most industrial services. At 415 V it still handles 121 kA, at 440 V it's 75.6 kA, and at 500 V or 690 V it drops to 17 kA. If your fault current at 480 V is above 17 kA, this breaker is not the right pick — you need a higher-rated frame.

Siemens 3VA1110-5ED32-0AH0 SENTRON MCCB, 100A, 3-Pole, 187kA
MPN3VA1110-5ED32-0AH0
Siemens SENTRON 3VA1110-5ED32-0AH0, 3-pole molded case circuit breaker, 100 A at 40 °C, TM210 thermal-magnetic release, 187 kA interrupting at 240 V AC.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA11105ED320AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AB12 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 100 A |
| Current at 45 °C | 100 A |
| Current at 50 °C | 100 A |
| Current at 55 °C | 98 A |
| Current at 60 °C | 96 A |
| Current at 65 °C | 94 A |
| Current at 70 °C | 91 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 75.6 kA |
| Breaking capacity at 500 V | 17 kA |
| Breaking capacity at 690 V | 17 kA |
| Power loss, max. | 25 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM210 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | nut keeper kit on both ends |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | Yes |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 3 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 20 000 |
| Height | 130 mm |
| Width | 76.2 mm |
| Depth | 70 mm |
| Height (in) | 5.12 in |
| Width (in) | 3 in |
| Depth (in) | 2.76 in |
Product details
MPN