It carries a 187 kA interrupting rating at 240 V, 121 kA at 415 V, and 75.6 kA at 440 V — the interrupting capacity drops to 17 kA at 500 V and 690 V. This is a current-production part (lifecycle stage: current).
The 100 A rating holds flat from 40 °C to 50 °C, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. At 240 V it clears 187 kA, enough for high-capacity transformer secondaries; at 415 V it clears 121 kA, typical for industrial distribution. The shunt trip allows remote tripping, useful for emergency-stop circuits or interlocking. The trip alarm switch signals a fault condition separately from the auxiliary position feedback. Power loss is 25 W maximum at rated current — factor that into the enclosure thermal budget, especially in a multi-breaker lineup.
The 3VA1110-5ED32-0JH0 measures 130 mm high, 76.2 mm wide, 70 mm deep. The 3-pole footprint matches standard SENTRON 3VA panel cutouts — no rewiring needed if swapping from a 3VA1110-5ED36-0AC0, since the mounting centers and terminal layout are identical within the same frame size.