Above that, it steps down: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. That means in a warm panel — say 55 °C internal — you still get 98 A of headroom, not the full 100 A. Plan your load margin accordingly. Breaking capacity is the headline: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. The 17 kA at 690 V still covers most industrial motor branch circuits. The shunt trip (STL) release is built in, so you can remotely trip the breaker via a control signal.
The basic switch variant is 3VA11105ED320AA0; this order code includes that switch plus the shunt trip.