Skip to main content
Siemens 3VA1110-5ED32-0KH0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA1110-5ED32-0KH0 Molded Case Circuit Breaker, 100

MPN3VA1110-5ED32-0KH0

SENTRON 3VA1110-5ED32-0KH0 molded case circuit breaker, 3-pole, 100 A at 40 °C, 121 kA breaking capacity at 415 V, line protection, 70 mm depth, 76.2 mm width.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-5ED32-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11105ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1110-5ED32-0KH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.25 W
3VA1110-5ED32-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1110-5ED32-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-5ED32-0KH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1110-5ED32-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-5ED32-0KH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The SENTRON 3VA1110-5ED32-0KH0 is a 3-pole molded case circuit breaker (MCCB) rated 100 A at 40 °C, with a breaking capacity of 121 kA at 415 V. It's designed for line protection — the kind of workhorse that sits in a main distribution panel or a motor control center, protecting feeders and branch circuits from short circuits and overloads. The 100 A continuous rating holds flat from 40 °C up to 50 °C, then derates gradually to 91 A at 70 °C, so you don't lose headroom in a warm enclosure.

Breaking capacity and what it means for your line

At 415 V, this MCCB interrupts 121 kA symmetrical. At 240 V it's even higher at 187 kA.

Width is a standard 3-inch footprint for a 3-pole frame, so it drops into existing SENTRON 3VA mounting bases or panel cutouts without re-drilling.

Auxiliary and trip options

It does not have an undervoltage release, so if you need undervoltage protection, you'd look at a different suffix. The trip indicator is present, so you get a visual flag when the breaker trips on fault.

Frequently asked questions

Where can I buy 3VA1110-5ED32-0KH0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 3VA1110-5ED32-0KH0 drop into a panel specified around 3VA1110-5ED32-0AA0 without rewiring?

Yes, both share the same 3-pole frame dimensions (76.2 mm width, 130 mm height, 70 mm depth) and mount on the same SENTRON 3VA base, so it's a direct mechanical swap. The wiring difference is the shunt trip coil on the -0KH0 variant — you'll need a control wire for that, but the power connections are identical.

MPN