Skip to main content
Siemens 3VA1110-5EE32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-5EE32-0DA0 SENTRON MCCB, 100A, 187kA at 240V

MPN3VA1110-5EE32-0DA0

Siemens SENTRON 3VA1110-5EE32-0DA0, 3-pole molded case circuit breaker, 100 A at 40 °C, TM220 thermal-magnetic release, 187 kA at 240 V, with undervoltage release, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-5EE32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11105EE320AA0

Ratings

3VA1110-5EE32-0DA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.27.5 W

Protection & Trip Unit

3VA1110-5EE32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1110-5EE32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-5EE32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1110-5EE32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-5EE32-0DA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

SENTRON 3VA1110-5EE32-0DA0 — 100 A MCCB with TM220 Release and Undervoltage Trip

The Siemens 3VA1110-5EE32-0DA0 is a 3-pole SENTRON molded case circuit breaker rated for line-protection duty, carrying a continuous current of 100 A at 40 °C through 50 °C before the thermal derating curve begins to pull it back — 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. That derating profile means the breaker holds its full rating across typical panel ambient conditions; you only lose headroom above 50 °C, which is useful to know when the breaker shares an enclosure with heat-generating contactors or drives. Breaking capacity is specified across five voltage points: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. The steep drop above 440 V is characteristic of a breaker whose arc-chamber and contact geometry are optimized for the 240–415 V range common in North American and European distribution panels. At 690 V the 17 kA figure still covers most motor branch-circuit fault levels, but verify against the available fault current at the point of installation. The TM220 overcurrent release is a thermal-magnetic type — the thermal element handles overload protection with a time-delay curve, while the magnetic element trips instantaneously on short-circuit. No electronic adjustment or communication function is built in; this is a fixed-trip breaker for straightforward line protection where you don't need selective coordination tuning via software.

Undervoltage Release and Auxiliary Release Design

This variant includes an undervoltage release (UVR) as the auxiliary release — designated as such in the design-of-auxiliary-release field. The UVR trips the breaker when the control voltage drops below a preset threshold, which is standard for applications where you need to guarantee that downstream loads de-energize on a brownout or loss of control power (e.g., machine safety circuits or motor starters that must not auto-restart). The trip indicator is not present on this order code, so there is no local mechanical flag showing the trip cause; you'd rely on the UVR's own status or a remote auxiliary contact if added.

Dimensions and Panel Fit

The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep — a 3-pole footprint that fits standard SENTRON 3VA mounting bases and busbar systems. The 76.2 mm width (3 inches) is the critical dimension for multi-pole grouping in a distribution panel; three of these side-by-side occupy 228.6 mm of DIN-rail or panel-mounting width. Depth of 70 mm (2.76 in) leaves clearance for rear-connected busbars or cable lugs without protruding past the enclosure depth limit.

Frequently asked questions

Where can I buy 3VA1110-5EE32-0DA0 and how do I get a price?

This part is sourced to order against an RFQ through independent industrial-automation distribution. Submit a request for quote (RFQ) with your quantity and target delivery window; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1110-5EE32-0DA0 at different voltages?

The breaker is rated for 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. The capacity is highest in the 240–415 V range and drops significantly above 440 V.

What does the TM220 release designation mean on this MCCB?

TM220 indicates a thermal-magnetic overcurrent release with fixed settings. The thermal element provides time-delayed overload protection; the magnetic element provides instantaneous short-circuit protection. There is no electronic adjustment or communication capability.

Does 3VA1110-5EE32-0DA0 include an undervoltage release?

Yes, this order code includes an undervoltage release (UVR) as the auxiliary release. It trips the breaker when control voltage drops below the dropout threshold, preventing automatic reclosure after a brownout or power loss.

What are the physical dimensions of this breaker?

The 3VA1110-5EE32-0DA0 measures 130 mm high, 76.2 mm (3 in) wide, and 70 mm (2.76 in) deep. The 76.2 mm width is the per-pole spacing for a 3-pole unit.

MPN
3VA1110-5EE32-0DA0