Skip to main content
Siemens 3VA1110-5EF32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-5EF32-0AG0 SENTRON MCCB, 100 A, 187 kA at 24

MPN3VA1110-5EF32-0AG0

Siemens SENTRON 3VA1110-5EF32-0AG0, molded case circuit breaker, 3-pole, 100 A rated continuous current, TM240 thermal-magnetic release, 187 kA interrupting at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-5EF32-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB11

Ratings

3VA1110-5EF32-0AG0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1110-5EF32-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1110-5EF32-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-5EF32-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1110-5EF32-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-5EF32-0AG0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Interrupting capacity across voltages

The 3VA1110-5EF32-0AG0: The interrupting rating is 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. That spread covers most industrial panel fault-current levels up to 690 V; at 415 V the 121 kA figure gives generous headroom above typical 50–65 kA SCCR requirements for motor control centers.

Thermal derating — what the numbers mean for panel loading

The breaker holds 100 A continuously from 40 °C through 50 °C without derating. At 55 °C it drops to 96 A, at 60 °C to 94 A, at 65 °C to 92 A, and at 70 °C to 90 A. If the panel ambient runs above 50 °C, the load must be trimmed accordingly — the 90 A floor at 70 °C is still usable for a 90 A feeder.

Dimensions and panel fit

At 130 mm high, 76.2 mm wide, and 70 mm deep, this MCCB fits the standard SENTRON 3VA1110 footprint. The 76.2 mm width (3 inches) matches the typical 3-pole MCCB cutout in a distribution panel; the 70 mm depth leaves room behind the gland plate for wiring without forcing a deeper enclosure.

Auxiliary contacts and environmental limits

It ships with one auxiliary switch plus one trip alarm switch (HP type). Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. Front protection is IP40, so it is suited for clean indoor panel environments but not for washdown zones.

Frequently asked questions

Where can I buy 3VA1110-5EF32-0AG0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through our independent distribution network. Submit an RFQ for current pricing and availability — stock and lead time are confirmed at quote time.

What is the closest functional second-source for 3VA1110-5EF32-0AG0?

The closest functional peer is 3VA1110-5EE32-0JA0, which shares the same 100 A frame, 3-pole count, and SENTRON series. The key difference is the overcurrent release: the -5EF32-0AG0 uses a TM240 release, while the -5EE32-0JA0 uses a different release variant. Verify the trip curve matches your coordination study before substituting.

Will 3VA1110-5EF32-0AG0 drop into a panel specified around 3VA1110-5EE32-0JA0 without rewiring?

Yes, the dimensions are identical (130 mm height, 76.2 mm width, 70 mm depth) and both are 3-pole SENTRON 3VA1110 frame breakers. The mounting footprint and lug centers are the same, so no rewiring is needed — just confirm the TM240 release matches your trip settings.

What compliance documentation does this brand provide for 3VA1110-5EF32-0AG0 (RoHS, REACH, UL, IEC)?

Siemens SENTRON MCCBs are designed to meet IEC 60947-2 and typically carry UL 489 listing. RoHS and REACH declarations are available from Siemens on request. The rated insulation voltage Ui is 800 V, confirming IEC compliance for 690 V systems.

MPN
3VA1110-5EF32-0AG0