Skip to main content
Siemens 3VA1110-5EF32-0JC0 — Molded Case Circuit Breakers (MCCB)

3VA1110-5EF32-0JC0 Siemens 3VA1 IEC Frame 160, 55kA @ 415V,

MPN3VA1110-5EF32-0JC0

Siemens 3VA1 IEC frame 160, breaking capacity class M, Icu=55kA @ 415V, 3-pole, line protection TM240, ATAM, In=100A overload protection Ir=70A...100A short-circuit protection Ii=5...10 x In, nut keeper kit, shunt trip (STL) 110-127V DC, AC 50/60Hz, 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

The Siemens 3VA1110-5EF32-0JC0 is an IEC frame 160 molded-case circuit breaker from the 3VA1 series, built for line protection with a thermal-magnetic TM240 trip unit. It's rated In=100A continuous, with overload pickup adjustable Ir=70A...100A and instantaneous short-circuit pickup Ii=5...10 x In. The breaking capacity class M delivers Icu=55kA at 415 VAC — enough for high-fault industrial distribution panels without cascading upstream breakers.

This 3-pole breaker ships with a factory-installed shunt trip (STL) rated 110-127 V DC/AC 50/60 Hz and two auxiliary switches (HQ).

The TM240 thermal-magnetic trip provides fixed magnetic pickup at 5 to 10 times In, which suits motor branch circuits and general distribution where you need moderate short-circuit withstand without nuisance tripping on inrush. The 55kA interrupting rating at 415 VAC puts it in the 'M' (medium) breaking capacity class per IEC 60947-2 — appropriate for main or sub-feed breakers in industrial switchboards where fault current runs high but not into the ultra-high range.

Frequently asked questions

What is the interrupting rating of this breaker?

Icu = 55 kA at 415 VAC, which is the 'M' breaking capacity class per IEC 60947-2.

What accessories come fitted on this order code?

It includes a shunt trip (STL) rated 110-127 V DC/AC 50/60 Hz, two auxiliary switches (HQ), and a nut keeper kit.

What is the overload and short-circuit adjustment range?

Overload protection Ir is adjustable 70A...100A; short-circuit protection Ii is adjustable 5 to 10 times In.

Where can I buy 3VA1110-5EF32-0JC0?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

MPN
3VA1110-5EF32-0JC0