Skip to main content
Siemens 3VA1110-5EF32-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-5EF32-0JH0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA1110-5EF32-0JH0

Siemens SENTRON 3VA1110-5EF32-0JH0, molded case circuit breaker, 3-pole, 100 A at 40 °C, 187 kA interrupting at 240 V, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-5EF32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11105EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1110-5EF32-0JH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.25 W
3VA1110-5EF32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1110-5EF32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-5EF32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1110-5EF32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-5EF32-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1110-5EF32-0JH0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C, with an interrupting capacity of 187 kA at 240 V.

Interrupting and Continuous Ratings

Interrupting capacity drops with voltage: 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500 V and 690 V. The continuous current holds at 100 A through 50 °C, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. This thermal profile is typical for a 100 A frame — the breaker doesn't need to be oversized for a 40 °C panel ambient, but above 50 °C the derating curve governs the actual load it can carry.

Dimensions are 70 mm depth, 76.2 mm width, and 130 mm height — a standard 3-pole MCCB footprint that mounts directly onto a DIN rail or panel-mount base in a distribution board.

Frequently asked questions

What are the key ratings of 3VA1110-5EF32-0JH0?

It is a 3-pole MCCB rated 100 A continuous at 40 °C, with interrupting capacity of 187 kA at 240 V, 121 kA at 415 V, and 75.6 kA at 440 V. Rated insulation voltage is 800 V.

Where can I buy 3VA1110-5EF32-0JH0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm landed-cost figure.

Will 3VA1110-5EF32-0JH0 fit in a panel designed for 3VA1110-5ED36-0AC0?

Both are 3-pole SENTRON MCCBs in the same 76.2 mm width and 130 mm height footprint, so the physical fit is identical. The difference is in the interrupting rating and accessory configuration — verify the required fault current and auxiliary switch count before substituting.

What compliance documentation is available for 3VA1110-5EF32-0JH0?

As a Siemens SENTRON MCCB, it carries the standard CE, UL, and CSA certifications for the class. RoHS and REACH declarations are provided with the documentation package. Specific certificate numbers are confirmed at order.

MPN
3VA1110-5EF32-0JH0