Breaking capacity is 187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V, so it handles high available fault current on the line side of a panel without needing a current-limiting upstream device.
At 55 °C it derates to 96 A, at 60 °C to 94 A, at 65 °C to 92 A, and at 70 °C to 90 A. The TM240 release has fixed time delay (tr min and tr max both 1 s), so it's a standard panelboard curve, not adjustable for coordination studies.
Width is 76.2 mm, depth 70 mm, height 130 mm — fits a standard 3-pole MCCB footprint on a DIN rail or bolted to a mounting plate. Comes with 2 auxiliary switches HP (high-performance) built in, which can be wired to a PLC input for status feedback or to a shunt trip circuit. No undervoltage release, no phase-failure detection, no communication module — this is a basic line-protection breaker, not a smart metering device.