Skip to main content
Siemens 3VA1110-5EF36-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-5EF36-0AE0 SENTRON MCCB, 100A, 3-Pole, TM240

MPN3VA1110-5EF36-0AE0

Siemens SENTRON 3VA1110-5EF36-0AE0, molded case circuit breaker, 3-pole, 100 A at 40 °C, TM240 thermal-magnetic release, interrupting rating 187 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-5EF36-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11105EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1110-5EF36-0AE0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.25 W
3VA1110-5EF36-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1110-5EF36-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-5EF36-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA1110-5EF36-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-5EF36-0AE0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Line protection MCCB with TM240 release

Rated 100 A continuously at 40 °C ambient, it holds that rating through 50 °C before derating begins — at 55 °C it's still good for 98 A, and at 70 °C it delivers 91 A. That thermal curve means you can mount it in a warm panel without oversizing the frame. The interrupting ratings are what set this frame apart: 187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. The auxiliary switch configuration supports up to 4 HQ auxiliary switches, though this unit ships without a trip indicator or undervoltage release.

Frequently asked questions

What is the interrupting rating of 3VA1110-5EF36-0AE0 at 240 V?

The interrupting rating is 187 kA at 240 V AC, which is exceptionally high for a 100 A frame.

Where can I buy 3VA1110-5EF36-0AE0 and how is it quoted?

This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

MPN
3VA1110-5EF36-0AE0