SENTRON 3VA1110-5EF36-0AH0 — 100 A MCCB with TM240 trip
Interrupting capacity is the headline here: 187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. Thermal derating is published per the datasheet: full 100 A up to 50 °C, then 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C.
Footprint and panel fit
Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — standard 3-pole MCCB footprint for a 100 A frame. Snaps onto DIN rail or bolts to a mounting plate; the 70 mm depth keeps it clear of shallow enclosure back panels.