The interrupting ratings are 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V, which covers most industrial distribution panels up to 690 V line-to-line.
The breaker holds 100 A from 40 °C through 50 °C, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. Physical envelope is 130 mm high, 76.2 mm wide, 70 mm deep; the 76.2 mm width is a standard 3-pole MCCB footprint for DIN-rail or screw-mount panels.
The integrated auxiliary trip module carries order code 3VA9608-0BB11 — that is the factory-matched accessory for this breaker.