Skip to main content
Siemens 3VA1110-5EF36-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-5EF36-0BH0 SENTRON MCCB, 100 A, 3-Pole, Line

MPN3VA1110-5EF36-0BH0

Siemens SENTRON, Molded case circuit breaker, 3VA1110-5EF36-0BH0, 3-pole, 100 A, TM240 overcurrent release, line protection, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1110-5EF36-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1110-5EF36-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1110-5EF36-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1110-5EF36-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-5EF36-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1110-5EF36-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-5EF36-0BH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The interrupting ratings are 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V, which covers most industrial distribution panels up to 690 V line-to-line.

The breaker holds 100 A from 40 °C through 50 °C, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. Physical envelope is 130 mm high, 76.2 mm wide, 70 mm deep; the 76.2 mm width is a standard 3-pole MCCB footprint for DIN-rail or screw-mount panels.

The integrated auxiliary trip module carries order code 3VA9608-0BB11 — that is the factory-matched accessory for this breaker.

Frequently asked questions

What is the breaking capacity of 3VA1110-5EF36-0BH0 at 415 V?

The interrupting rating at 415 V is 121 kA.

Where can I buy 3VA1110-5EF36-0BH0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the rated current of 3VA1110-5EF36-0BH0 at 40 °C?

The rated continuous current Iu is 100 A at 40 °C.

MPN