Thermal derating and operating envelope
The 3VA1110-5EF36-0JH0: This breaker carries its full 100 A rating from 40 °C up through 50 °C. At 55 °C it derates to 98 A, at 60 °C to 96 A, at 65 °C to 94 A, and at 70 °C to 91 A.
Auxiliary functions and release options
The trip indicator is present. It does not include an undervoltage release or ground-fault monitoring. For a controls integrator: the shunt trip lets a PLC or safety relay cut power remotely, while the auxiliary switches provide status feedback to the control system.