Skip to main content
Siemens 3VA1110-5FF42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-5FF42-0AA0 SENTRON 4-Pole MCCB, 100 A, 187 k

MPN3VA1110-5FF42-0AA0
Active

Siemens SENTRON 3VA1110-5FF42-0AA0, 4-pole molded case circuit breaker, 100 A continuous, TM240 thermal-magnetic release, 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-5FF42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1110-5FF42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.25 W
3VA1110-5FF42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1110-5FF42-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-5FF42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1110-5FF42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-5FF42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

It carries 100 A continuous at 45 °C ambient — that's the current it passes without tripping in a warm panel. At 50 °C it still holds 100 A; at 55 °C it derates to 98 A, at 60 °C to 96 A, at 65 °C to 94 A, and at 70 °C to 91 A (–). If your panel runs hot, that derating curve is the one that decides fit, not the nominal 100 A. The interrupting capacity is the headline number that matters for fault clearing: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V (–). The TM240 thermal-magnetic release gives adjustable short-circuit pickup up to 1000 A. The N-conductor protection is set at 50%.

DIN-rail panel fit — dimensions and integration

At 70 mm deep, 101.6 mm wide, and 130 mm tall, this 4-pole MCCB fits standard SENTRON panel footprints. The width is the critical dimension for DIN-rail spacing: 101.6 mm is exactly 4 inches — a standard 4-module width on most DIN-rail mounting plates. Depth of 70 mm leaves room behind the gland plate for wiring and busbar connections.

Frequently asked questions

Where can I buy 3VA1110-5FF42-0AA0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Will 3VA1110-5FF42-0AA0 drop into a panel specified around 3VA1110-5ED32-0AA0?

Both are 4-pole SENTRON MCCBs in the same 3VA frame family, so the mounting footprint and DIN-rail spacing are identical. The main difference is the release: this one carries a TM240 thermal-magnetic release, while the 5ED32 variant uses a different release type. If the panel was wired for the same 100 A rating and 4-pole configuration, it will physically fit without rewiring, but verify the release curve matches your protection coordination.

What is 3VA1110-5FF42-0AA0's interrupting capacity at 240 V?

187 kA at 240 V. That is the maximum fault current it can safely interrupt at that voltage level.

MPN