Thermal derating and power loss
The 3VA1110-5GF42-0AA0: The breaker carries its full 100 A up to 50 °C ambient; above that it derates linearly to 91 A at 70 °C. Maximum power loss is 25 W — a figure to account for in enclosed panel heat budgets, especially when multiple breakers stack on a DIN rail.
Mounting and protection
Front-face protection is IP40 — suitable for dry indoor panels where tools or fingers won't contact live parts. The 4-pole design handles three-phase plus neutral in a single unit, common for main disconnects in 400 V distribution boards. No undervoltage release or ground-fault monitoring is built in; those are external add-ons if the application requires them.