Siemens 3VA1110-5MH36-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-5MH36-0BA0 Circuit Breaker, 55kA @ 415V, 100

MPN3VA1110-5MH36-0BA0

Siemens 3VA1 IEC frame 160, breaking capacity class M, Icu=55kA @ 415V, 3-pole, starter protection TM120M, AM, In=100A, without overload protection, short-circuit protection Ii=5...15 x In, clamp connection, undervoltage release (UVR) 24V DC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

The Siemens 3VA1110-5MH36-0BA0 is a 3-pole IEC frame 160 circuit breaker from the 3VA1 series, rated at 100 A with a breaking capacity class M delivering Icu=55kA @ 415V. It is configured for starter protection with a TM120M thermal-magnetic release, set for short-circuit protection only (no overload protection) with an adjustable instantaneous trip Ii=5...15 x In. The unit includes a 24V DC undervoltage release (UVR) and clamp-type terminals for wiring.

Breaking capacity and coordination

The 55 kA Icu at 415 V places this breaker in the 'M' (medium) breaking capacity class within the 3VA1 frame 160 family. For a site electrical engineer, this means it can safely interrupt fault currents up to 55 kA without upstream cascading — sufficient for most industrial secondary distribution panels where the available fault current is below that threshold. The 100 A continuous rating and the TM120M trip unit are sized for motor starter protection, where the breaker provides short-circuit backup while the overload relay handles running protection.

Integration notes

The clamp-type terminals accept copper or aluminum conductors without lug kits, reducing installation time in the panel. The undervoltage release (UVR) at 24 V DC allows remote tripping from a safety circuit or PLC output — common in machine-tool and conveyor applications where a loss of control voltage must open the breaker. The 3-pole configuration fits standard DIN-rail or panel-mount footprints for the 3VA1 frame 160.

Frequently asked questions

What is the breaking capacity of this circuit breaker?

The ultimate breaking capacity Icu is 55 kA at 415 V AC, placing it in the 'M' (medium) class for the 3VA1 frame 160. This rating governs its ability to safely clear a short-circuit fault without damage.

Where can I buy the 3VA1110-5MH36-0BA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer.

Does this breaker include overload protection?

No. The TM120M release is configured for short-circuit protection only (Ii=5...15 x In). Overload protection must be provided by a separate overload relay in the motor starter circuit.

MPN