Skip to main content
Siemens 3VA1110-5MH36-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-5MH36-0CC0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA1110-5MH36-0CC0

Siemens SENTRON 3VA1110-5MH36-0CC0, molded case circuit breaker, 3-pole, 100 A at 40 °C, interrupting capacity 187 kA at 240 V, starter protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-5MH36-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11105MH360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1110-5MH36-0CC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.27.5 W

Protection & Trip Unit

3VA1110-5MH36-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM120M
Overcurrent protection functionI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1110-5MH36-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-5MH36-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1110-5MH36-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-5MH36-0CC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Panel fit and integration

The 3VA1110-5MH36-0CC0 measures 70 mm deep, 76.2 mm wide, and 130 mm high — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures. The 76.2 mm width (3 inches) matches the typical 3-pole MCCB slot in a Siemens SENTRON distribution panel. Depth at 70 mm means it clears most shallow enclosures, but verify the door clearance for the handle mechanism. It includes an undervoltage release (UVR) and two auxiliary switches HQ, so factor those into wiring — the UVR needs a control voltage to keep the breaker closed, and the aux switches provide status feedback to a PLC or annunciator.

Thermal derating and power loss

The breaker is rated 100 A at 40 °C, 45 °C, and 50 °C — no derating needed up to 50 °C. Above that, it drops to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. If your panel ambient runs hot (say, inside a non-ventilated enclosure near a motor), size the breaker to the derated value, not the 100 A nameplate. Maximum power loss is 27.5 W — that's the heat it dumps into the enclosure at full load, so factor it into your thermal budget. Storage range is -40 °C to 80 °C; operating range is -25 °C to 70 °C.

MPN
3VA1110-5MH36-0CC0