Skip to main content
Siemens 3VA1110-6ED32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-6ED32-0AA0 SENTRON MCCB, 100 A, 3-Pole, 220

MPN3VA1110-6ED32-0AA0
Active

Siemens SENTRON 3VA1110-6ED32-0AA0, molded case circuit breaker, 3-pole, 100 A, TM210 overcurrent release, 220 kA breaking capacity at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-6ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1110-6ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.25 W
3VA1110-6ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1110-6ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-6ED32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1110-6ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-6ED32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Line protection MCCB with TM210 release

Breaking capacity is the headline spec here: 220 kA at 240 V AC, 154 kA at 415 V, 121 kA at 440 V, and still 17 kA at 690 V. That puts this breaker well into high-fault-duty territory — suitable for main feeders or sub-distribution where SCCR requirements are stiff. The 3-pole form factor (76.2 mm wide, 130 mm tall, 70 mm deep) mounts on a DIN rail or direct-panel with standard busbar connections.

Above that, derating is gradual: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Storage range is -40 to 80 °C, wider than the operating envelope. That matters for spares stored in unheated warehouses or shipped through cold climates. Maximum power loss is 25 W. In a dense panel with multiple breakers, that heat adds up — account for it in the enclosure thermal calculation.

Frequently asked questions

What is the breaking capacity of 3VA1110-6ED32-0AA0 at 415 V?

154 kA at 415 V AC, with 220 kA at 240 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V.

What does the TM210 release designation mean?

TM210 indicates a fixed thermal-magnetic overcurrent release — thermal element for overload protection, magnetic element for short-circuit protection — with no adjustable trip settings. It is factory-set for line protection duty.

Where can I buy 3VA1110-6ED32-0AA0?

Sourced and quoted to order against an RFQ through independent distribution channels. Submit a request for current pricing and availability.

MPN
3VA1110-6ED32-0AA0