Skip to main content
Siemens 3VA1110-6ED32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-6ED32-0AB0 SENTRON MCCB, 80 A, 4-Pole, 76 kA

MPN3VA1110-6ED32-0AB0

Siemens SENTRON 3VA1110-6ED32-0AB0, Molded case circuit breaker, 4-pole, 80 A, TM210 release, 76 kA at 240 V, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-6ED32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA11106ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11
3VA1110-6ED32-0AB0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V5 kA
Breaking capacity at 690 V5 kA
3VA1110-6ED32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
3VA1110-6ED32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-6ED32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1110-6ED32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-6ED32-0AB0 — Mechanical
ParameterValue
Height130 mm
Width (in)4 in

Product details

Its 4-pole construction handles three-phase plus neutral, and the interrupting ratings climb to 76 kA at 240 V AC — enough to clear high-fault scenarios in distribution panels without upstream coordination headaches. At 415 V the breaker still holds 53 kA, dropping to 32 kA at 440 V and 5 kA at 500 V or 690 V. That steep fall-off above 500 V means this variant is best suited for 240 V or 400/415 V lineups where the available fault current stays under 53 kA. The TM210 release is fixed thermal-magnetic — no electronic adjustment, no communication module, no voltage-trip or ground-fault monitoring. It is a straightforward line-protection breaker for panels where simplicity and reliability beat configurability.

At 55 °C it derates to 78 A, then 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. That flat top through 50 °C is useful for enclosures with moderate heat rise — no need to oversize for a warm panel. Height is 130 mm, width 4 in — a standard footprint for 4-pole MCCBs in North American and IEC panels. No undervoltage release or shunt trip is fitted on this order code — if you need those, this is not the variant.

MPN
3VA1110-6ED32-0AB0