Skip to main content
Siemens 3VA1110-6ED32-0JA0 — Molded Case Circuit Breakers (MCCB)

3VA1110-6ED32-0JA0 Siemens 3VA1 100A Circuit Breaker, 70kA @

MPN3VA1110-6ED32-0JA0

Siemens 3VA1 IEC frame 160 MCCB, 3-pole, breaking capacity class H, Icu=70kA @ 415V, line protection TM210, In=100A fixed, Ir=100A fixed, Ii=10 x In, with left-side shunt trip 110-127 V AC/DC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

What this 3VA1 MCCB carries

The Siemens 3VA1110-6ED32-0JA0 is a 3-pole IEC frame 160 molded case circuit breaker with a 100 A fixed thermal-magnetic trip unit (TM210). Overload protection Ir is fixed at 100 A; short-circuit protection Ii is fixed at 10 x In (1000 A). This order code includes a factory-installed left-side shunt trip accessory rated 110–127 V AC 50/60 Hz / DC. The shunt trip allows remote or emergency-off tripping from a pushbutton, PLC output, or safety relay, which is common in machine disconnect or conveyor line-stop circuits.

Availability is through normal Siemens distribution channels.

Frame 160 means the breaker body is sized for busbar or cable connections up to 160 A rated continuous current, but this unit is fitted with a 100 A trip — so the frame gives thermal headroom for high ambient or non-fan-cooled enclosures. The fixed thermal-magnetic trip (TM210) means no interchangeable trip unit; overload and short-circuit settings are not field-adjustable. That simplifies ordering but locks the protection curve — confirm 100 A continuous and 1000 A magnetic pickup match your load's inrush and cable protection requirements. The shunt trip sits on the left side of the breaker. It draws power from a separate 110–127 V AC/DC source, not the breaker's own line side. Wire it through a normally-open emergency-stop contact or PLC relay; energizing the shunt trip coil mechanically trips the breaker. Verify the control voltage matches your panel's auxiliary supply — 110 V is common in North American control transformers; 127 V appears in some IEC markets.

Frequently asked questions

What are the key ratings for this MCCB?

Icu = 70 kA @ 415 V AC (breaking capacity class H), In = 100 A fixed, Ir = 100 A fixed (overload), Ii = 10 x In (1000 A) fixed short-circuit pickup. The shunt trip is rated 110–127 V AC 50/60 Hz / DC.

Where can I buy the 3VA1110-6ED32-0JA0 and how is it quoted?

We source this Siemens MCCB to order against an RFQ. Availability and current pricing are confirmed at quote time — send your target quantity and delivery window for a firm quote.

What compliance documentation is available for this part?

As a Siemens 3VA1 series MCCB, it carries IEC 60947-2 certification. RoHS and REACH declarations are standard from Siemens. UL listing varies by variant — confirm with the order code's specific UL file when required for North American installations.

MPN
3VA1110-6ED32-0JA0