Skip to main content
Siemens 3VA1110-6ED42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-6ED42-0AA0 SENTRON MCCB, 100A 4P, 220kA at 2

MPN3VA1110-6ED42-0AA0
Active

Siemens SENTRON 3VA1110-6ED42-0AA0, molded case circuit breaker, 4-pole, 100 A, TM210 thermal-magnetic release, line protection version, 220 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1110-6ED42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1110-6ED42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.25 W
3VA1110-6ED42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1110-6ED42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-6ED42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1110-6ED42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-6ED42-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

The Siemens 3VA1110-6ED42-0AA0 is a SENTRON molded case circuit breaker rated for continuous current of 100 A at ambient temperatures up to 50 °C without derating — at 55 °C it still holds 98 A, and at 70 °C it delivers 91 A. The 4-pole configuration with a TM210 thermal-magnetic release makes this a line-protection breaker for main feeders or large sub-distribution in 3-phase + N systems. The interrupting ratings are the headline: 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V, dropping to 17 kA at 500 V and 690 V.

The 101.6 mm width (4 inches) is the standard 4-pole MCCB footprint for this SENTRON frame size — it occupies four 25.4 mm pole spaces on a DIN rail or panel-mount base. Depth of 70 mm leaves clearance for rear-mounted busbars or cable ladders behind the breaker.

Selectivity and coordination notes

The TM210 release is a fixed thermal and fixed magnetic type — no interchangeable trip units, so the 100 A rating is hard-set at the factory.

Frequently asked questions

What is the interrupting capacity of 3VA1110-6ED42-0AA0 at 240 V?

220 kA at 240 V, which allows placement at the service entrance of high-fault industrial panels without upstream current-limiting fuses.

What is the closest functional alternative to 3VA1110-6ED42-0AA0?

The 3VA1110-5ED32-0AA0 is a 3-pole version of the same frame and release — same 100 A TM210, same interrupting ratings, but three poles instead of four. If your panel was wired for 4-pole, the 5ED32 will not drop in without reworking the neutral conductor path.

Where can I buy 3VA1110-6ED42-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What compliance documentation does Siemens provide for 3VA1110-6ED42-0AA0?

Siemens SENTRON MCCBs carry IEC 60947-2 certification and are designed to meet UL 489 requirements. RoHS and REACH declarations are available from Siemens support documentation.

MPN
3VA1110-6ED42-0AA0