Skip to main content
Siemens 3VA1110-6EE32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-6EE32-0AA0 SENTRON MCCB, 100 A, 3-Pole, 220

MPN3VA1110-6EE32-0AA0
Active

Siemens SENTRON 3VA1110-6EE32-0AA0, molded case circuit breaker, 3-pole, 100 A, TM220 thermal-magnetic release, 220 kA interrupting at 240 V, line protection, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-6EE32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1110-6EE32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.25 W
3VA1110-6EE32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1110-6EE32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-6EE32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1110-6EE32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-6EE32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The TM220 thermal-magnetic release handles overload and short-circuit curves without a separate trip unit — set it and forget it for fixed-threshold distribution panels. Interrupting capacity hits 220 kA at 240 V, dropping to 154 kA at 415 V and 121 kA at 440 V — still well above typical utility fault levels for most industrial services. At 690 V it holds 17 kA, so it's usable on 480Y/277 V or 600 V delta systems within that ceiling. The 3-pole footprint measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard SENTRON 3VA frame that drops into existing 3VA panel cutouts without re-drilling.

Rated 100 A from 40 °C through 50 °C; above that it derates linearly to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. The storage limits govern handling and warehousing, not running conditions.

Frequently asked questions

What is the width of 3VA1110-6EE32-0AA0?

76.2 mm (3 inches).

Will 3VA1110-6EE32-0AA0 drop into a panel specified around 3VA1110-5ED32-0AA0 without rewiring?

Both are 3-pole SENTRON 3VA frame MCCBs with the same 76.2 mm width, 130 mm height, and 70 mm depth — mechanical fit is identical. The difference is the overcurrent release: the -6EE32 carries a TM220 thermal-magnetic release, while the -5ED32 uses a different release variant. Verify the trip curve matches your coordination study before swapping.

MPN
3VA1110-6EE32-0AA0