Skip to main content
Siemens 3VA1110-6EE46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-6EE46-0AA0 SENTRON MCCB, 100 A, 4-Pole, 220

MPN3VA1110-6EE46-0AA0
Active

Siemens SENTRON 3VA1110-6EE46-0AA0, molded case circuit breaker, 4-pole, 100 A, TM220 release, 220 kA at 240 V, 154 kA at 415 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-6EE46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1110-6EE46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.25 W
3VA1110-6EE46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1110-6EE46-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-6EE46-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1110-6EE46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-6EE46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

Siemens 3VA1110-6EE46-0AA0 — 100 A, 4-Pole SENTRON MCCB with TM220 Release

The Siemens 3VA1110-6EE46-0AA0 is a 4-pole SENTRON molded case circuit breaker rated for 100 A continuous at 45 °C, with a TM220 thermal-magnetic release. The 70 mm depth and 101.6 mm width fit standard panel footprints; the IP40 front protection keeps debris out of the enclosure cutout.

Interrupting Capacity and Coordination

At 240 V the 3VA1110-6EE46-0AA0 clears 220 kA, dropping to 154 kA at 415 V and 121 kA at 440 V. The TM220 release has an adjustable li max of 1,000 A, letting the installer tune the magnetic trip for motor inrush or transformer energization without nuisance trips.

Rated 100 A at 45 °C and 50 °C, the breaker derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. The maximum power loss is 25 W.

Frequently asked questions

Where can I buy 3VA1110-6EE46-0AA0 and get current pricing?

This part is sourced and quoted to order against an RFQ. Submit a request through our independent distribution channel; availability and current pricing are confirmed at quote time — no online stock or price figure is published here.

What is the interrupting rating of 3VA1110-6EE46-0AA0 at 415 V?

At 415 V it interrupts 154 kA, and at 240 V it clears 220 kA.

What compliance documentation does Siemens provide for 3VA1110-6EE46-0AA0?

Siemens provides RoHS and REACH declarations, plus IEC 60947-2 test certificates and UL listing documentation through the SENTRON series. Specific document downloads are available via the Siemens Industry Online Support portal.

MPN
3VA1110-6EE46-0AA0