At 415 V the rating drops to 154 kA, at 440 V to 121 kA, and at 690 V to 17 kA, so the voltage class of your distribution system directly determines which interrupting rating applies. The continuous current rating holds flat at 100 A from 40 °C through 50 °C ambient, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C.
The 3VA1110-6EF32-0AH0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard MCCB footprint that mounts in a panel or enclosure via the SENTRON busbar system. The TM240 release is factory-set for line protection; there is no undervoltage release, no voltage trigger, no ground fault monitoring, and no communication function, so this is a straight thermal-magnetic breaker for basic feeder or branch-circuit protection.