Siemens 3VA1110-6EF32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-6EF32-0JA0 SENTRON MCCB, 100A, 220kA at 240V

MPN3VA1110-6EF32-0JA0

Siemens SENTRON 3VA1110-6EF32-0JA0, 3-pole molded case circuit breaker, 100 A rated at 40 °C, 220 kA breaking capacity at 240 VAC, line protection with TM240 thermal-magnetic release and shunt trip.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-6EF32-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11106EF320AA0

Ratings

3VA1110-6EF32-0JA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.25 W

Protection & Trip Unit

3VA1110-6EF32-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1110-6EF32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-6EF32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1110-6EF32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-6EF32-0JA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB is and what it carries

The Siemens SENTRON 3VA1110-6EF32-0JA0 is a 3-pole molded case circuit breaker (MCCB) designed for line protection, fitted with a TM240 thermal-magnetic overcurrent release and a shunt trip (STL) auxiliary release. Rated 100 A continuously at 40 °C, it derates to 91 A at 70 °C — the thermal curve matters if this breaker lives in a hot enclosure or next to other heat sources. Breaking capacity is 220 kA at 240 VAC, 154 kA at 415 V, 121 kA at 440 V, and holds 17 kA all the way up to 690 V — that 690 V figure is the one to check for 600 V class installations where most MCCBs drop off sharply. Rated insulation voltage is 800 V, and maximum power loss is 25 W — factor that into enclosure thermal calculations if the panel is densely packed.

Panel fit and environment

Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a standard MCCB footprint that drops into most SENTRON panelboards and distribution blocks without re-drilling. Operating range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. The storage minimum matters if the breaker sits in an unheated warehouse before installation.

Frequently asked questions

What type of overcurrent release does this MCCB use?

A TM240 thermal-magnetic release, with a shunt trip (STL) auxiliary release for remote tripping.

MPN