Skip to main content
Siemens 3VA1110-6EF36-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-6EF36-0AD0 SENTRON MCCB, 100 A, 3-Pole, 220

MPN3VA1110-6EF36-0AD0

Siemens SENTRON 3VA1110-6EF36-0AD0, molded case circuit breaker, line protection, 3-pole, 100 A, TM240 release, 220 kA at 240 V, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-6EF36-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1110-6EF36-0AD0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 690 V17 kA
3VA1110-6EF36-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1110-6EF36-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-6EF36-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1110-6EF36-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-6EF36-0AD0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Line-side protection for high-fault panels

The Siemens SENTRON 3VA1110-6EF36-0AD0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current, designed for line protection in distribution and motor control center applications. The TM240 thermal-magnetic release provides adjustable long-time delay (tr max 1 s) and fixed instantaneous pickup, covering cable and busbar protection in industrial switchgear. Breaking capacity reaches 220 kA at 240 V AC and 154 kA at 415 V AC — figures that tell you this breaker handles fault levels typical of large transformer secondaries or high-capacity bus risers without needing upstream current-limiting fuses.

Rated continuous current holds at 100 A from 40 °C through 50 °C ambient. Above that, derate linearly: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, 90 A at 70 °C. The operating temperature range spans -25 °C to 70 °C, with storage from -40 °C to 80 °C.

Physical fit and auxiliary contacts

Dimensions: 130 mm height, 76.2 mm width, 70 mm depth. The 76.2 mm width (3-inch footprint) is standard for 3-pole MCCBs in this class — it fits existing SENTRON mounting bases and busbar kits without adapter plates. Three HQ auxiliary switches are integrated, giving you status feedback for remote monitoring or interlocking without an add-on module.

Frequently asked questions

Where can I buy the 3VA1110-6EF36-0AD0 and how is it quoted?

This MCCB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here.

What is the breaking capacity of the 3VA1110-6EF36-0AD0 at different voltages?

Breaking capacity is 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V. These ratings cover high-fault installations like transformer secondaries and bus risers.

Does the 3VA1110-6EF36-0AD0 drop into a panel specified for the 3VA1110-5EE32-0JA0?

The -6EF36-0AD0 carries a TM240 release and 3 HQ auxiliary switches, while the -5EE32-0JA0 has a different release and aux contact configuration. Verify the trip curve and auxiliary wiring before substituting without a full panel review.

MPN
3VA1110-6EF36-0AD0